Planning LION System
EN1Z-0921GE51 R0315
8
Planning
Overview
Engineering with CARE
During CARE engineering, the type of I/O modules, terminal
assignment and module configuration are defined
depending on the application. The same applies to
engineering with COACH (which is possible starting with
COACH version 2.02).
Planning
In this step, the following has to be defined, if applicable:
Power supply
Fusing
Earth grounding
Lightning protection
Panel Bus wiring
Design of a L
ONWORKS network
Design of a C-Bus network
Useful accessories
Cable selection
Transformer Selection
NOTE: In Europe, the system transformer(s) must be
safety isolating transformers according to
IEC61558-2-6.
In the U.S.A. and Canada, NEC Class-2
transformers must be used.
Current Requirement
When selecting the appropriate transformer, take into
account the number of individual modules, accessories, and
field devices in determining the total current requirement.
Devices powered
Current requirement
24 VAC 24 VDC
CLLIONLC01 with
CLMMI00N22 (backlight ON)
and with watchdog load (max.
500 mA)
690 mA 640 mA
CLLIONLC01 with
CLMMI00N22 (backlight ON)
but without watchdog load
190 mA 140 mA
…821 130 mA 80mA
…822 160 mA 90 mA
…823 180 mA 130 mA
…824 140 mA 90 mA
…825 140 mA 90 mA
CLIOP830A 200 mA 95 mA
Table 10 Current requirement of LION System components
depending on power supply
Connectable Power Supplies
CentraLine CRT Series (Europe)
Transformer Primary side Secondary side
CRT 2 220/230 VAC 24 VAC, 50 VA, 2 A
CRT 6 220/230 VAC 24 VAC, 150 VA, 6 A
CRT 12 220/230 VAC 24 VAC, 300 VA, 12 A
Table 11 CentraLine CRT series transformers data