Part No.: 4417584_Rev12 Configuration Manual
CIU 888 3 - 73
$*6
13.Click the Floating Roof Level tab, the Properties detail appears.
You can view or edit these properties:
Relative pressure Select if applicable.
Pressure address Enter product pressure transmission address.
Pressure TOI Select: B, C, E, or M*.
Pressure TOR Select: ZP1*.
Product Pressure in fore-
ground
scan
Check to enable the Pressure in foreground
scan.
* Refer to TABLE 3-1 for additional information.
Properties Description
Floating Roof Enabled Check to enable floating roof levels scan.
Floating Roof Level
address
Enter floating roof level transmission address.
Floating Roof level 1 TOI The TOI of the first floating roof level (B)
Floating Roof level 1
TOR
The TOR of the first floating roof level (ZHN)
Floating Roof level 2 TOI The TOI of the second floating roof level (B)
Floating Roof level 2
TOR
The TOR of the second floating roof level (ZHO)
Floating Roof level 3 TOI The TOI of the third floating roof level (B)
Floating Roof level 3
TOR
The TOR of the third floating roof level (ZHP)
Floating roof level in fore-
ground
scan
Set the floating roof to be scanned in the foreground or
background. Default background.
CAUTION:
Setting Floating roof levels scan in foreground would
have impact on the product level and other measure-
ments scan rate.
* Refer to TABLE 3-1 for additional information.