Part No.: 4417584_Rev12 Configuration Manual
CIU 888 3 - 75
$*6
3.2.10.2 Configuring Dual Gauges
The CIU 888 supports collection of Product Level data from an
additional BPM gauge and this data is exposed to its Modbus output
(Modbus RTU and Modbus TCP/IP) based on the configuration. Using
this mechanism, any Modbus host system can get the data from CIU
888 and visualize it in its user interface.
To add an additional level gauge to a tank, a GPU data-input should be
configured again as described in Section 3.2.10.1 . The additional
gauge only supports configuration of Level parameter. Configuration of
TOR B = Alarm status + [contact status] if TOI is C or E +
product level.
C = Alarm status + [contact status] if TOI is C or E +
temperature.
J = Alarm status + water level.
L = Alarm status + [contact status] if TOI is C or E +
signed level.
M = Water alarm status + [contact status] if TOI is C or
E + water level status + water level record.
ZAG = Average vapour temperature (854, 873, 877,
970, 971 & 973 only).
ZLQ = Innage servo level (854 only).
ZQQ = Abbreviated hydrostatic density (854, 866, 873,
877, 970, 971 & 973 only).
ZP3 = Pressure sensor P3 (854, 866, 873, 877, 970,
971 & 973 only).
ZP1 = Pressure Sensor P1 (854, 866, 873, 877, 970,
971 & 973 only)
Special Characters Description