Part No.: 4417584_Rev12 Configuration Manual
CIU 888 3 - 106
$*6
6. Enter the details as required and click Apply.
NOTE: Click the Apply button after filling details in Tanks, Entities, Temperature
Profiles and Density Profiles tab.
3.2.14.2 Delete TCP/IP Modbus map
On the CIU 888 node, right-click and select Delete exisiting TCP/
IP modbus map from the menu.
Absolute start address This indicates the absolute start address of the Modbus
tank record.
Values are in decimal.
Note: For Entis Pro and ENTIS Complaint Modbus
mapping, if the number of tanks are more than 50 then
configure absolute start address as 10000.
Temperature Profile Abso-
lute Start address
This indicates the absolute start address of the tem-
perature profiles record.
Values are in decimal. Default value is 20000. Configu-
rable when modbus mapping is User Specified.
Temperature Profile
Record Interval
This indicates the record interval of the temperature
profiles record.
Values are in decimal. Default value is 125. Configu-
rable when modbus mapping is User Specified.
Density Profile Absolute
Start address
This indicates the absolute start address of the density
profiles record.
Values are in decimal. Default value is 30000.
Configurable when modbus mapping is User Specified.
Density Profile Record
Interval
This indicates the record interval of the density profiles
record.
Values are in decimal. Default value is 320.
Configurable when modbus mapping is User Specified.
Fields Description