Appendix H - Creation of new Modbus field device / TRL/2 Field Device
Part No.: 4417584_Rev12 Configuration Manual
CIU 888 H - 42
H.15 Valid Register Ranges
The following table indicates the valid consecutive Modbus register
address ranges in the device.
H.16 Modbus Map
The following table indicates the Modbus register map of the device that
can be scanned by CIU.
<DeviceInformation>
<DeviceUnits>
<Unit>
<UnitDetail>
<UnitName>
This specifies the device
engineering unit. Refer to
section H.19 for the supported
units.
For LEVEL : m, cm,
mm, ft, yard, in, in/16,
fis, fii/256, in/256,
1/10 mm (TRL/2)
For TEMPERATURE :
°C, °F, K, Tenth
Fahrenheit (TRL/2),
Tenth Celsius (TRL/2)
For DENSITY : kg/m³,
°API, lb/ft³, RD60, lb/
US gal, kg/l, gr/ml
For PRESSURE : kgf/
cm², Pa, kPa, psi, atm,
bar, psi_r100,
psi_r1000, mBarG
(TRL/2), mBarA (TRL/
2), 1/100 psiG (TRL/
2), 1/100 psiA (TRL/2)
<DeviceInformation>
<DeviceUnits>
<Unit>
<UnitDetail>
<Resolution>
This specifies the device
engineering unit's resolution.
-127 to 128
XML Tag
Description
Possible Values
<ValidRegisterRanges>
<Range>
<StartRegisterAddress>
This indicates the Modbus
Start address
300001 to 365535
400001 to 465535
<ValidRegisterRanges>
<Range>
<EndRegisterAddress>
This indicates the Modbus End
address
300001 to 365535
400001 to 465535
XML Tag
Description
Possible Values
<DeviceInformation>
<ModbusMap>
<Name>
This indicates the name of
the parameter in the Modbus
field device which needs to
be scanned by CIU.
Any String
XML Tag
Description
Possible Values