Getting Started
Part No.: 4417584_Rev12 Configuration Manual
CIU 888 3 - 33
5. Click the BPM Field Port tab, the Properties detail appears.
You can view or edit these properties:
6. Click the RS Field Port tab, the Properties detail appears.
You can view or edit these properties:
Properties Description
Sensitivity Enter sensitivity in the range of 1 through 7 (default =
7).
Baud rate Select 1200, 2400, or 4800.
Turn around delay When CIU 888 receives a response from a field instru-
ment (in a field port) it waits for this time period before
sending a new request on the same field port.
Enter time in ms (default = 20 ms).
Time out Enter timeout in ms (default = 250 ms).
Retries Enter number of retries in the range of 1 through 10
(default = 3).
Properties Description
Baud rate Select 1200, 2400, 4800, 9600, 19200, or 38400
Mode Select RS 232 or RS 485 (default = RS-232C).
Turn around delay Enter reply waiting time in ms (default = 20 ms).