Getting Started
Part No.: 4417584_Rev12 Configuration Manual
CIU 888 3 - 56
$*6
Refer to the following table for information on different WCF methods
Density of calibration weights Brass density is used in some of the stan-
dardized mass/weight conversion meth-
ods. It is the density of used calibration
weights.
Default: 8000 kg/m3
Note:
- Unit of measure is always kg/m3
CTL format This setting indicates the format of CTL
(VCF) that gets presented from CIU.
Selection:
Standard calculations – CTL value would
be preseted with 5 decimal digits when
value is less than 1 and 4 decimal digits
when value is greater than 1.
Always 4 decimals – CTL value would be
presented with 4 decimal digits.
Always 5 decimals - CTL value would be
presented with 5 decimal digits.
Default: Standard calculations
WCF Method This setting indicates the method to calcu-
late Weight Correction Factor and thereby
calculate Weight.
Selection: (NONE | OIML R125 | API
MPMS CH11.5 | SIMPLIFIED | CUSTOM)
Default: NONE
WCF Method
TankAirDensity
(kg/m3)
VapDensity
(kg/m3)
AirBrassDensity
(Density of calibration
weights)
(kg/m3)
Remarks
NO WCF 0 0 0
OIML R125 TankAirDensity TankAirDensity 8000 The value of Dair is
configurable in the Global
settings.
Properties Description