EasyManua.ls Logo

Honeywell DC33XB - Input 1 Parameters Set up Group; Table 3-7 Input 1 Group Function Prompts

Honeywell DC33XB
95 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration
12/00 UDC3300 Basic Model: DC33XB User Manual 29
3.8 Input 1 Parameters Set Up Group
Table 3-7 Input 1 Group Function Prompts
Function
Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
IN1 TYPE
Input 1 Actuation Type
For Input Range
Minimum and Maximum
see Appendix E
DISABL W TC H
B TC W TC L
E TC H 100 PT
E TC L 100 LO
J TC H 200 PT
J TC L 500 PT
K TC H RAD RH
K TC L RAD RI
NNM H 0-20mA
NNM L 4-20mA
NM90 H 0-10mV
NM90 L 0-50mV
NIC TC 0-5 V
R TC 1-5 V
S TC 0-10 V
T TC H CARBON
T TC L OXYGEN
0-10mV
XMITTER1
Transmitter
Characterization
B TC S TC
E TC H T TC H
E TC L T TC L
J TC H W TC H
J TC L W TC L
K TC H 100 PT
K TC L 100 LO
NNM H 200 PT
NNM L 500 PT
NM90 H RAD RH
NM90 L RAD RI
NIC TC LINEAR
R TC SQROOT
LINEAR
IN1 HI
Input 1 High Range Value
(Linear Inputs only)
999. to 9999. floating
(in engineering units)
1000
IN1 LO
Input 1 Low Range Value
(Linear Inputs only)
999. to 9999. floating
(in engineering units)
0
RATIO 1
Input 1 Ratio 20.00 to 20.00
(floats to 3 decimal places)
1.000
BIAS IN1
Input 1 Bias 999. to 9999.
(in engineering units)
0
FILTER 1
Input 1 Filter 0 to 120 seconds 1
BURNOUT1
Burnout Protection NONE DOWN
UP NO_FS
NONE
EMISSIV1
Emissivity 0.01 to 1.00 0.00

Table of Contents

Related product manuals