Configuration
36 UDC3300 Basic Model: DC33XB User Manual 12/00
3.13 Alarms Set Up Group
Table 3-12 Alarms Group Function Prompts
Function
Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
A1S1 VAL
Alarm 1, Setpoint 1 Value Value in Engineering Units 90
A1S2 VAL
Alarm 1, Setpoint 2 Value Value in Engineering Units 10
A2S1 VAL
Alarm 2, Setpoint 1 Value Value in Engineering Units 95
A2S2 VAL
Alarm 2, Setpoint 2 Value Value in Engineering Units 5
A1S1TYPE
Alarm 1, Setpoint 1 Type NONE
INP 1
INP 2
PV (Process Variable)
DEV (Deviation)
OUTPUT
SHED
EV ON (Event On – SP
Program)
EV OFF (Event Off – SP
Program)
MANUAL
REM SP (Remote Setpoint)
F SAFE (Failsafe)
PVRATE (PV Rate of Change)
BREAK
NONE
A1S2TYPE
Alarm 1, Setpoint 2 Type Same as A1S1TYPE NONE
A2S1TYPE
Alarm 2, Setpoint 1 Type Same as A1S1TYPE NONE
A2S2TYPE
Alarm 2, Setpoint 2 Type Same as A1S1TYPE NONE
A1S1 H L
Alarm 1, Setpoint 1 State LOW
HIGH
HIGH
A1S1 EV
SP Programming Event
Alarm State for Alarm 1,
Setpoint 1
BEGIN
END
- -
A1S2 H L
Alarm 2, Setpoint 1 State LOW
HIGH
LOW