Position Proportional Calibration
12/00 UDC3300 Basic Model: DC33XB User Manual 71
Step Operation Press Action
7
DO AUTO
Set 100 %
value
FUNCTION
LOOP 1/2
The increment relay is turned on to move the motor to
100 % position.
Upper Display: (Counts of Feedback Slidewire-0 to 3000)
Lower Display: SPAN VAL
When the motor stops, the display should stop counting,
then go to step 12.
8
DO MAN
Set 0 % value
FUNCTION
LOOP 1/2
You will see:
Upper Display: (The existing zero calibration value in
counts)
Lower Display: ZERO VAL
9
or
until the desired zero value is reached in the upper
display.
Upper Display: (The desired zero value)
Lower Display: ZERO VAL
10
DO MAN
Set 100 %
value
FUNCTION
LOOP 1/2
The controller will store the 0% value and you will see:
Upper Display: (The existing span calibration value in
counts)
Lower Display: SPAN VAL
11
or
until the desired span value is reached in the upper
display.
Upper Display: (The desired span value)
Lower Display: SPAN VAL
For manual calibration, the motor does not move from its
position prior to the start of Position Proportional
calibration.
12
Exit the
Calibration
Mode
FUNCTION
LOOP 1/2
The controller will store the 100 % value.
LOWER
DISPLAY
or
SETUP
To exit the calibration mode.