4-28
4. CONFIGURATION
SUB-MATRIX PARAMETER CLASSIFICATION
CHART
0% ZONE
100% ZONE

DEFINITION:
Defines chart zone for printing.
HOW TO MODIFY IT:
Enter a new value.
POSSIBLE CHOICES:
0...100% - - - - > 0...80% for 0% zone of paper - - - - > 20...100% for 100%
zone.
The choice of parameters for 0% and 100% zone allows you to define the
datum such that the width of the chart paper is less than the calibrated
width of the paper.
This function permits the segregation of input traces into zones to avoid
the problem of input signals using the same paper scale and having the
same values printed on top of each other.
The minimum width per zone is 20% of the chart.
NOTE:
The zoning is only possible in TREND mode.
SEE ALSO:
PRINTER matrix and PRINT MODE parameter.
SUB DIV = NO DIVISION when zoning is < 100%
SUB-MATRI
X
PARAMETER CLASSIFICATION
CHART
0% ZONE
100% ZONE

EXAMPLE:
100% ZONE 1
0% ZONE 2
100%
ZONE 2
0%
ZONE 1