Periphery components for ESSER FACP
54 TI 798960.GB0 / 04.20
Specifications
*3
Operating voltage
:
4 x 3.6 V (AA) batteries
Battery lifetime
:
approx. 3 years
Current consumption
:
approx. 50 µA
Frequency band
:
433/868 MHz
Range : up to 300 m outdoors,
up to 30 m in buildings
Transmission power
:
max. 10 mW
Usage temperature
:
-5 °C ... +55 °C
Storage temperature - without batteries
- with batteries
:
:
-20 °C ... +70 °C
+25 °C ± 10 °C
Humidity
:
95% rel. humidity (non-condensing)
IP rating
:
IP 42
Material
:
ABS-V0
Colour
:
white (similar to RAL 9010)
Weight
:
approx. 315 g (incl. batteries)
Dimensions ( x H)
:
135 mm x 88 mm, incl. fire detector
VdS approval
:
G 205112
Specification
:
EN 54-18 : 2005 / -25 : 2008
VdS approval
:
G 205112
Declaration of Performance :
DoP-20622140326
*3
The information applies for the entire series incl. .MAR, .N0, .NU etc.