C300 faceplate indicators/displays
FTE activity LEDs
166 Experion C300 Controller User's Guide R301.1
Honeywell 11/06
Faceplate
Display
Indicates…
C300 Module
State
(PCMSTATE)
IDLE
Application mode with database loaded, all EEs good with
controller in IDLE – CDA present
CEEIDLE
OK
Application mode with database loaded, all EEs good with
controller in RUN – CDA present
CEERUN
BKUP
Application mode with database loaded, all EEs good,
module is secondary – CDA present
BACKUP
SF
See Note 4
One or more soft fail conditions are present in the C300
Controller. This state is independent of both CEE state
and Redundancy state.
SOFTFAIL
Note 1: (####) – This symbol does not appear on the C300 Controller faceplate display. It
appears on Control Builder and operator (Station) displays representing the C300 Controller to
indicate that the C300 Controller is OFFNET and this data is not available at this time. Controller
will continue to display the existing or changing faceplate display indication per the current
controller state. As a result of communication failure, CDA will return OFFNET as C300 Module
State.
Note 2: The controller is ‘lonely’ (cables disconnected or network related problem). Startup halts
until controller can obtain an IP address or validate an internally retained IP address.
Note 3: When a non-redundant controller reboots into the FAIL state, it assumes the backup IP
Address.
Note 4: SF indicates an on-line diagnostic soft failure, such as Battery status, Hardware
Watchdog timer timeout, IOLINK failure, etc.
FTE activity LEDs
Each FTE port on the C300, Series C FIM and Ethernet Switch have one status LED. The
bi-color FTE A and B LEDs indicate connectivity (link present) and communication
activity (transmit and/or receive). Table 10 describes the indications of the FTE Status
LEDs.
Table 10 FTE Activity LED Indications
FTE A and B
LEDs
Indicates…
RED
Link integrity check failed – No Ethernet signal detected, or cable is not
connected.