Initiating C300 Controller Shutdown
CEE Icon states in the Monitoring tab
176 Experion C300 Controller User's Guide R301.1
Honeywell 11/06
Step Action
Alternate methods:
Click the Toggle State toolbar button to set the selected item inactive.
Select Operate -> Change State
CEE Icon states in the Monitoring tab
The CEE status in the monitoring tab is indicated by the following versions of the CEE
icon.
CEE Icon States
Icon Color Corresponding CEESTATE Values
1. Project Tree Gray N/A
2. Loaded, not monitoring Gray N/A
3. Communication Failure Red N/A
4. InActive Blue CEESTATE = IDLE
5. Active Green CEESTATE = RUN
6. Configuration Error Red CEESTATE = FAIL, NOT_LOADED
Initiating C300 Controller Shutdown
Use the following procedure to initiate a shutdown command to the C300 Controller,
which results in the C300 Controller rebooting to its RDY state or boot firmware.
ATTENTION
Shutting down the C300 Controller, interrupts the transfer of data to the
Experion system. Be sure your system can tolerate the loss of live data, while
the C300 Controller is in its RDY state.
Step Action
1
Using Control Builder, select the Monitoring tab –
Double-click the C300 Controller icon to open the C300 Block configuration