R301.1 Experion C300 Controller User's Guide 211
11/06 Honeywell
C300 Controller Maintenance
This section includes information about replacement of the C300 Controller module and
associated IOTA.
C300 Controller module and IOTA replacement
To replace a non-redundant controller module
CAUTION
This procedure can only be performed while off process.
We recommend that you proceed with extreme caution whenever replacing
any component in a control system. Be sure the system is offline or in a safe
operating mode.
Component replacements may also require corresponding changes in the
control strategy configuration through Control Builder, as well as downloading
appropriate data to the replaced component.
Step Action
1
Loosen screws at each side of the plastic cover that secures the controller
module to the IOTA board. Remove the Controller module from the IOTA
board and connector.
2
Insert the new controller module onto IOTA board making sure that the
controller circuit board mates properly with the IOTA board connector.
Secure the controller module to the IOTA board with two screws located at
each side of the plastic cover.
3
The new controller will boot-up to ALIVE or NODB state.
4
Load firmware which is the same version as was running in the old controller.
5
In Control Builder, perform a ‘Load with Contents’ to the controller.