7707_05252017_F
DIMENSIONS
13H x 8.5”W x 4.5”D
(33cmH x 21.5cmW x 11.4cmD)
WEIGHT
5.8 lbs (2.6 kilograms)
excluding battery
13 lbs (5.9 kilograms) with
10 Ah battery
RADIO FREQUENCY
Standard Frequency Range:
450-470 MHz
Contact AES for other UHF
and VHF frequencies
ANTENNA
2.5 dB tamper resistant antenna
included, mounts on enclosure
Optional remote mounting
antenna available
POWER INPUT
AC SOURCES
Transformer: Class 2
16.5V AC nominal output
1.9 A max current (40 VA MIN)
ELK ELK-TRG1640,
MG ELECTRONIC SALES MGT1640,
or AES 1640 (not included)
DC SOURCES (includes FACP)
24V DC Regulated Power Supply
with Subscriber
Rechargeable Battery
1.9 A max current
BACKUP BATTERY
10-12 Ah, UL recognized lead acid
gel cell, size based on subscriber
configuration
PORTS
Ethernet for configuration
and message communication
USB access for software upgrade
REMOTE ANNUNCIATOR
AES Model 7740
Remote Annunciator, supervised
COMPATIBLE RECEIVERS
7705i AES-MultiNet Receiver
CONFIGURATION INTERFACE
Web browser capable device
accessible via smartphone, tablet,
laptop, or PC
CURRENT CONSUMPTION
Standby w/ charged backup battery:
200 mA (1.2 A Transmitting)
Standby + charging backup battery:
900 mA (1.9 A Transmitting - MAX)
POWER OUTPUT
2 or 5 Watts
Factory set
ENCLOSURE MATERIAL
Steel with paint finish
FINISH COLOR
Red
VISUAL INDICATORS
Front panel LCD
(2 x 20 alphanumeric character
backlit display)
Power and Trouble LEDs
(ALM, Trouble, Tx, Rx, WA)
ALARM SIGNAL INPUTS/ZONES
· 8 individually programmable
E.O.L. type zone inputs
· 4+4: 4 reverse polarity input and
4 individually programmable
E.O.L. type zone inputs
· Optional 7794A AES-IntelliPro for
full data via Contact ID, Pulse,
Modem IIe and Modem IIIa2
UL LISTINGS
UL 864 10
th
Edition
Standard for Control Units and
Accessories for Fire Alarm Systems
ULC S559-04 1
st
Edition
Equipment for Fire Signal
Receiving Centres and Systems
TROUBLE OUTPUT—ACK
DELAY/ANTENNA CUT
Form C relay, fail secure, rated 24V
DC 1A resistive, unsupervised
RESET BUTTON
Located on main circuit board
OPERATING TEMPERATURE
32 to 12F (0 to 49°C)
STORAGE TEMPERATURE
14 to 140°F (-10 to 60°C)
RELATIVE HUMIDITY
0 to 93%, non-condensing
RECHARGE CAPABILITY
Will charge 12V battery size
from 10-12 Ah
Technical Specifications 7707 Fire
Contact Us
For pricing and availability or to learn more about IntelliNet 2.0, please call your local
AES Sales Representative at (800) 237-6387 or email sales@aes-corp.com.