90 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Programming Master Programming Level
3.6.8 Annunciators
Pressing 3 while viewing Programming Screen #3 will cause the control panel to display the following
screens:
A printer module, graphic annunciator module, LCD annunciator module, LED annunciator module, and relay module can be pro-
grammed into the ES-200X system. These devices communicate with the FACP over the ANN-BUS terminals on the control panel.
ANN-BUS Setup
Two ANN-BUS circuits are available on the ES-200X. Press 1 to configure the Primary ANN-BUS or press
2 to configure the Secondary ANN-BUS. The following screens will be displayed for either ANN-BUS cir-
cuit where (XXX) indicates either Primary or Secondary.
ANN-BUS Enabled
The ANN-BUS must be enabled if any modules are connected to the ANN-BUS terminals. To enable the ANN-BUS, press 1 while
viewing ANN-BUS screen #1 so that the display reads ANN XXX Enabled Yes. Each press of the 1 key will cause the display to toggle
between ANN XXX Enabled Yes and ANN XXX Enabled No.
Modules Installed
If an ANN-BUS module is installed, press 2 for Modules Installed to select ANN-BUS addresses for the
module(s). The only difference between the two programming screens are the addresses. The Primary Bus
module addresses will have a prefix of “1-” while the Secondary Bus module addresses will have a prefix
of “2-”. The following screen will be displayed for either bus circuit.
Pressing the down arrow key will allow the programmer to view additional screens displaying Addresses 1-8. To select one or more
addresses for the installed module(s), press the number key corresponding to the module address in each screen. The following screen
will be displayed for each address:
OFF_NORMAL_MESSAGE 308 000 000 LB LX
24_HOUR_TEST 602 000 000 RP
24 HOUR ABNORMAL TES 608 000 000 RY
UPDOWN REQUEST 411 000 000 RB
UPLOAD SUCCESS 416 000 000 RS
DOWNLOAD SUCCESS 412 000 000 RS
UPDOWN FAILURE 413 000 000 RR
GENERAL ALARM 000 000 000 00 00
GENERAL SUPERVISORY 000 000 000 00 00
Table 3.3 Event Codes (Continued)
PROGRAMMING
1=HISTORY
2=COMMUNICATOR
3=ANNUNCIATORS
Programming Screen #3
ANN-BUS SELECT
1=PRIMARY
2=SECONDARY
3=ANN-BUS OPTIONS
ANNUNCIATORS
1=PRIMARY
2=SECONDARY
3=ANN-BUS OPTIONS
Annunciators Screen
ANN XXX
1=ENABLED NO
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN-BUS Screen #1
ANN XXX
1=CLASS A NO
ANN-BUS Screen #2
ANN XXX
1=ENABLED NO
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN XXX Screen #1
ANN-BUS MODULES
1=ADDR. X-1 NONE
2=ADDR. X-2 NONE
3=ADDR. X-3 NONE
ANN-BUS Modules Screen #1
ANN-BUS MODULE X-1
ANN-BUS ADDRESS
1=TYPE NONE
ANN-BUS Address Screen