Programming
108 MS-9050UD PN 52413:C 01/23/08
Pressing 1 while viewing the ANN-I/O Address Screen will program the annunciator module to
annunciate either Point (addressable device address) information or Zone information. Each
press of the 1 key will toggle the display between Zone and Point.
Pressing 2 while viewing the ANN-I/O Address Screen will select the Point range to be
annunciated (refer to the tables in "ANN-I/O Zone Option" on page 108 and "ANN-I/O Point
Option" on page 109). If Point has been selected, each press of the 2 key for Range will change
the points to be annunciated with the options being 01 - 30 and 31 - 50.
Note that if Zone has been selected, the 2 key will have no effect since the only zones that can
be annunciated are 00 - 19. The range cannot be changed.
ANN-I/O Zone Option
If Zone is selected as the module option, the first ten LEDs on the first ANN-I/O module will
display the system status information. The remaining 19 LEDs on the module will display the
active/alarm status of each zone. The LED assignments for the ANN-I/O module will be as
follows.
Module LED Function
1 AC Fault
2Fire Alarm
3 Supervisory
4 Trouble
5 Alarm Silenced
6Not Used
7Not Used
8Not Used
9Not Used
10 Not Used
11 Zone 00 - Active/Alarm
12 Zone 01 - Active/Alarm
13 Zone 02 - Active/Alarm
14 Zone 03 - Active/Alarm
15 Zone 04 - Active/Alarm
16 Zone 05 - Active/Alarm
17 Zone 06 - Active/Alarm
18 Zone 07 - Active/Alarm
19 Zone 08 - Active/Alarm
20 Zone 09 - Active/Alarm
21 Zone 10 - Active/Alarm
22 Zone 11 - Active/Alarm
23 Zone 12 - Active/Alarm
24 Zone 13 - Active/Alarm
25 Zone 14 - Active/Alarm
26 Zone 15 - Active/Alarm
27 Zone 16 - Active/Alarm
28 Zone 17 - Active/Alarm
29 Zone 18 - Active/Alarm
30 Zone 19 - Active/Alarm
31 Not Used
32 Not Used
33 Not Used
34 Not Used
35 Not Used
36 Not Used
37 Not Used
38 Not Used
39 Not Used
40 Not Used