Operating Instructions
MS-9050UD PN 52413:C 01/23/08 161
Pressing the down arrow key, while viewing the screen shown above, will allow the operator to
view additional programming information about the selected device, such as:
Enable/Disable Status
Device Type
Alarm Verification On/Off (for detectors)
Walktest Yes/No
PAS (Positive Alarm Sequence) Yes/No (for detectors only)
Pre-Signal Yes/No (for detectors and monitor modules)
Zone Assignments (five maximum)
Adjective/Noun descriptor
Silenceable Yes/No (for control modules)
4.22.2 Zones
Pressing 2 while viewing Read Status Screen #1 will cause the following screens to be displayed:
From the preceding screens, the control panel operator can view:
Zones Installed - all software zones programmed into the system (20 maximum)
Zones Enabled - all software zones that are enabled
Zones Disabled - all software zones that have been disabled
Special Purpose - on or off programming for Special Purpose Zones 17 reserved for PAS, 18
reserved for Pre-signal and 19 reserved for Two Stage Operation
Zone Type - the Type assigned to each installed zone (default is Alarm)
READ STATUS
1=SYSTEM POINT
2=ZONES
3=POWER
Read Status Screen #1
ZONES
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zones Screen #1
ZONES
1=SPECIAL PURPOSE
2=ZONE TYPE
3=FUTURE USE
Zones Screen #2