Canadian Application
MS-9050UD PN 52413:C 01/23/08 205
APPENDIX H Canadian Application
H.1 ANN-LED Annunciator Installation for Canadian Applications
The FACP is supplied with a Dress Panel and one ANN-LED annunciator
When installing and programming the FACP, the Canadian Option must be set to ON prior to
any other panel programming (refer to "Canadian Option" on page 102 of the Programming
Section of this manual)
The optional ANN-LED annunciators must be adjacent and close-nippled to the FACP with
the wiring in metal conduit.
For the optional remote annunciators, a ground wire must be daisy-chained between circuit
board mounting screws on each annunciator and then connected from the last annunciator
board to the Earth Ground stud in the FACP backbox.
The installer must write in the Date of Final Assembly on the Master Marking and Warranty
Label located on the FACP backbox door
Figure H.1 FACP Minimum Configuration - Single ANN-LED Annunciator
FACP
ANN-LED Annunciator
m_9050UDann_led.cdr
Figure H.2 FACP Maximum Configuration - Five ANN-LED Annunciators
FACP
Optional ANN-LED annunciators must be adjacent
and close-nippled to FACP with wiring in conduit.
Supplied ANN-LED
Annunciator
Optional ANN-LED Annunciators
m_9050UDtoann_led4.cdr
metal conduit