FocusPRO
TM
TH6110 / TH6220 / TH6320
7
System test System status
Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted.
Press s / t to turn system on/off.
Press NEXT to advance to next test.
Press DONE to terminate system test.
Test number System status
10
0
To begin, press and hold the s and t
buttons until the display changes.
Installer setup
Setup function Settings & options (factory default in bold)
Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted.
9 Stage 1 compressor
cycle rate (CPH)
3 Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
10 Stage 2 compressor
cycle rate (CPH)
3 Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
12 Manual/Auto
changeover
0 Manual changeover (Heat/Cool/Off)
1 Auto changeover (Heat/Cool/Auto/Off) **See page 8
2 Auto changeover only (Auto) **See page 8
13 Adaptive Intelligent
Recovery
1 On**See page 8
0 Off
14 Temperature
display
0 Fahrenheit
1 Celsius
15 Compressor
protection
5 Five-minute compressor off time **See page 8
[Other options: 0, 1, 2, 3 or 4-minute off time]
16 Schedule format 0 5/2 (programmable weekdays and weekends)
1 5/1/1 (weekdays, Saturday & Sunday programmable)
27 Heat temperature
range stops
90 Max. heat temperature setting is 90° F (32° C)
[Other options: 40 �F to 89 �F (4.5 �C to 31.5 �C)]�F to 89 �F (4.5 �C to 31.5 �C)]F to 89 �F (4.5 �C to 31.5 �C)]�F (4.5 �C to 31.5 �C)]F (4.5 �C to 31.5 �C)]�C to 31.5 �C)]C to 31.5 �C)]�C)]C)]
28 Cool temperature
range stops
50 Min. cool temperature setting is 50° F (10° C)
[Other options: 51 �F to 99 �F (10.5 �C to 37 �C)]�F to 99 �F (10.5 �C to 37 �C)]F to 99 �F (10.5 �C to 37 �C)]�F (10.5 �C to 37 �C)]F (10.5 �C to 37 �C)]�C to 37 �C)]C to 37 �C)]
Installer system test
10 Heating system 0 Heat and fan turn off.
1 Stage 1 heat turns on. Fan turns on if Setup Function 1 is set to 1,
5, 9 or 10 OR Setup Function 3 is set to 1 **See page 6
2 Stage 2 heat turns on
3 Stage 3 heat turns on - TH6320U only
20 Emergency heating
system
0 Heat and fan turn off
1 Heat and fan turn on
2 Stage 2 heat turns on (auxiliary heat) - TH6220D only
30 Cooling system 0 Compressor and fan turn off
1 Compressor and fan turn on
2 Stage 2 compressor turns on
40 Fan system 0 Fan turns off
1 Fan turns on
CAUTION: Compressor protection is bypassed during testing. To prevent equipment
damage, avoid cycling the compressor quickly.