GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019 25
5824 Serial/Parallel Printer Interface Module Installation Control Panel Installation
4.6 5824 Serial/Parallel Printer Interface Module Installation
You can use the 5824 Serial/Parallel Printer Interface Module to connect a printer to the panel. Printing is available for real-time events,
detector status and event history. To install the 5824 Serial/Parallel Printer module, do the following steps:
1. Make sure power is off at the panel.
2. Connect the 5824 module to the panel as shown in Figure 4.15.
3. Use the DIP switches on the back of the 5824 board to assign an ID# to the 5824 (see Section 4.8.1).
4. Configure the 5824 device through programming. See Section 4.6.1.
5. Connect a printer to the 5824 as shown in Figure 4.15.
Figure 4.15 5824 Module Connection to the Panel
4.6.1 Selecting 5824 Options
To configure the 5824 module, do the following steps:
1. Add the module to the System. JumpStart
®
will add the module automatically (see Section 6.1). You can also add it manually (see
Section 7.2.2).
2. Select a name, if desired (see , "Naming Modules").
3. Select options for the printer and the output port. See below.
Printer and Output Port Options
1. From the Main Menu, select 7 for Program Menu.
2. Select 1 for Module.
3. Select 1 for Edit Module.
4. From the list that displays, select the 5824 module you want to configure.
5. Press <Enter> to bypass the next two screens. A screen similar to the one shown in Figure 4.16 will display.
Figure 4.16 Selecting Printer and Output Port Options
6. Select options for the printer as needed for your installation. Most printers are parallel.
7. If you use a serial printer, use the next screen to select serial port options as required for your printer. Refer to your printer manual
if you need more information.
NOTE: Use four 5824s per panel maximum.
Parallel
Cable
connectors to
connect to the
printer
Serial
DIP Switches
Model 5824 Board
Supervised
Class A Power-Limited
Option Choices
Baud Rate: 75 - 19200
Data Bits: 5 - 8
Stop Bits: .5, 1, 2
Parity: None, Even, Odd
Table 4.4 Serial Printer Options