GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019 49
Modules Programming
7.2.4 Changing Module Options
Each module has a unique set of options that specifically applies to the functionality of the module you edit.
1. Use the <Right> arrow key to move the cursor between available options.
2. To edit the Option settings, press the <Up> or <Down> arrows.
7.2.5 Adding a Module
You must access the Main Menu to add a Module. If necessary, enter the Installer Code. If you need to add a new hardware module to the
system, follow the steps below.
1. Enter the Installer Code.
2. Select 7 for Program Menu.
3. Press 1 to enter the Module Menu.
4. Press 2 to add a module.
5. From the next screen, use the <Up> or <Down> arrows to choose a Module Type to add from the <New Module Type> screen.
6. The screen will display Adding module [#]...” for a few moments. You will be returned to the <New Module Type> screen where
you can select another module if desired.
7. You must save changes when you exit the Program Menu or you cannot add the new module.
NOTE: If you add a module that has not been physically connected, the panel will go into trouble after it reinitializes (when you exit the
Program Menu). When the new module is attached, the trouble will automatically correct itself.
7.2.6 Deleting a Module
If you need to delete a module, follow these steps.
You must access the Main Menu to perform this task. If necessary, enter the Installer Code.
1. Enter the Installer Code.
2. Select 7 for Program Menu.
3. Press 1 to enter Module Menu.
4. Press 3 to delete a module.
5. From the next screen, select a module to delete. A warning screen displays.
6. If you want to proceed to delete the module, select <Ye s> . To cancel, select <No>.
7.2.7 View Module List
1. Enter the Installer Code.
2. Select 7 to access the Program Menu.
3. Press 1 to enter Module Menu.
4. Press 4 to view Module List.
7.2.8 Zone
Through the Zone Option in the Program Menu you can edit, add, delete, and view Zone Points. If you make selections in this option, it
will affect all detectors and switches in the zone. Up to 125 zones can be used in the system.
7.2.9 Edit Zone
You can used the Edit Zone option to edit the following features:
To edit a zone, follow these steps:
1. Enter the Installer Code.
2. Select 7 for the Program Menu.
3. Press 2 to enter the Zone Menu.
4. Press 1 to edit a Zone.
5. Enter the Zone Number, then press <Enter>.
7.2.10 Edit Zone Name
1. To edit the Zone Name, press 1.
2. You can use text to display a descriptive name for the zone.
3. To edit names, refer to Appendix Appendix A:.
7.2.11 Edit Zone Properties
Zone properties consist of alarm delay characteristics, and heat detector sensitivity.
1. Do steps 1 through 5 of Section 7.2.9.
2. Press 2 to edit the properties of the selected zone.
Range: 135-190°F (Velociti)
Figure 7.2 Edit Zone Properties
zone name zone properties (which includes, zone type, and detector sensitivity) zone accessory
Detection type also selected from this screen (see Table 7.2).