64 GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019
System Operation Basic Operation
.
Figure 8.3 Checking Detector Sensitivity Compliance
8.4.11 View Status of a Point
1. From the Main Menu, select 2 for Point Status.
2. From the list that displays, press <Enter> to select the module where this point is located. The screen that displays will show you if
the point has a trouble and will provide sensitivity compliance information. (See Section 8.4.10 for
3. Complete the information about detector sensitivity compliance.
8.4.12 View Alarms, Supervisories or Troubles
When the system is in alarm, (supervisory or trouble), press <Down> arrow to view the location of an alarm, supervisories or trouble.
8.4.13 View System Information
Press 8 from the Main Menu to view the panel model, serial number, system version number and date. Press the <Left> arrow key to
return.
About the Panel
Press 1 to access the About Panel to view the panel model, serial number, system version number and date.
Send/Receive Firmware Updates
The GWF-7075 has the ability to be updated in the field. The latest GWF-7075 Firmware Update Utility can be downloaded from the
Gamewell-FCI Web Site.
1. Press 2 to send a firmware update or press 3 to receive a firmware update from the System Information Menu.
2. Use the <Up> or <Down> arrow key to select a panel to send/receive an update to/from. Press <Enter> to start the update process.
Feature Activation
Use this Menu to activate/register additional features.
1. Press 4 from the System Information Menu. This option displays the Feature Activation Menu.
2. Press 1 to enter a six digit activation code or press 2 to review the features already activated in this panel.
SMOKE ION 1.1%
MODULE_33 OINT_4
[2001 ] [M33:004 ] A058
NORMAL >= MORE
ATL-151 (1.1% OB/FT)
ACA=057 M=093 T=109
Clear Air=-58 <01%)
Peak-061 (04%) >=HLP
CO SMOKE 2.0%
MODULE_33 SENSOR_ 4
[2001 ][M33:004 ] AXXX
Sensitivity = 2.0%
CO – xxx ppm
SMOKE ION --------%
MODULE_33 POINT_4
[2001 ][M33:004 ] A058
CAL TRBLE >= MORE
ATL-151 (----% OB/FT)
ACA=-57 M=093 T=109
Clear Air=058 (01%)
Peak-061 (04%) >=HLP
ATL-Alarm Threshold
ACA=-Average Clr Air
M=Maint Threshold
T =Trouble Threshold
Example of Compliant Detector
Example of a Non-Compliant Detector
Possible States:
NORMAL - Detector sensitivity-UL Compliant
(and not in alarm)
ALARM - Detector in alarm
CAL MAINT - Detector needs maintenance, but not
yet in Trouble
CAL TRBLE - Detector-NFPA non-compliant (Other
Trouble messages, for example,
“MISSING” could override this
message.
Example of Compliant CO Detector
To access Help Display,
press <Right Arrow>
Detector ID
Fields
Indicates percent
obscurity per foot.
Detector ID
Fields
State of
Detector
Indicates percent
obscurity per foot.
Indicates percent
obscurity per foot.
To access Next
Display, press
<Right Arrow>.
To access Next
Display, press
<Right Arrow>.
Blanks signify a Non-
Compliant Detector.
CAL-indicates
the Detectors
are non-
compliant with
UL