GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2013 Honeywell International Inc. All rights reserved.
www.gamewell-fci.com CS-2045 Rev. C page 1 of 2
RCE-95
Relay Control Element
APPROVED
MEA
Approved
7300-1703:0135
SIGNALING
S521
FM
Description
The Gamewell-FCI Relay Control Element (RCE-95) is the
interface between the Gamewell-FCI, 600 Series and
IL95-E3 Series
®
Fire Alarm Control Panel (FACP) analog
circuits and building functions such as door holders, eleva-
tors, dampers, motors and disconnects. The RCE-95
offers feedback input points for positive confirmation of the
controlled device’s activity. For annunciation and feedback
at the panel, Gamewell-FCI offers a Relay Control Display
(RCD). The RCD is only available with the IdentiFlex 632
and IF650 FACPs.
The RCE-95 can be either surface or flush mounted and
has an integral LED which annunciates upon device
activation.
Operation
The devices connect to the SLC circuit of the FACP via a
two-wire non- polarized circuit. In its quiescent mode, the
RCE-95 monitors its internal circuitry for status of the
device itself and supervises an external control circuit for
status.
When a status change is detected, the event can be pro-
grammed to display on the optional RCD module (IF632
and IF650 only). When an event is reported to the control
panel that requires the activation of the RCE-95, the con-
trol panel communicates via the analog circuit to the RCE-
95 for activation. The integral LED is also lit for annuncia-
tion at the device.
Programming
The RCE-95 is programmed by setting a single DIP switch
easily accessible on the RCE-95s printed circuit board.
The DIP switch is used to set the address of the device. All
other programming is accomplished at the Fire Alarm Con-
trol Panel, either through a laptop computer or the control
panel operators display. (600 Series only).
E3 Series® is a registered trademark of Honeywell International Inc.
Microsoft® Windows® is a registered trademark of Microsoft® Corporation.
Features
Compatible with the Gamewell-FCI, 600 Series and
ILI95-E3 Series analog addressable FACPs
Supports Form-C dry relay contacts
Offers event or manual controllable relay functions
Provides positive feedback of relay activation
Contains LED annunciates activation
Is fully supervised
Has surface or flush mounting
Field programmable
Style 4, 6, or 7 wiring
Includes Screw terminals for field wiring connections