GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2045 Rev. C page 2 of 2
www.gamewell-fci.com
Mounting
The RCE-95 is designed to mount in a standard 4.688"
(11.908 cm) electrical backbox. The RCE-95 should be
mounted in an easily visible location so that the built-in
LED indicators may be easily seen and display the proper
connection and device activation.
Engineer’s Specifications
A programmable interface device shall be provided for the
control and status reporting of programmed relay control
functions. The RCE-95 shall communicate with the Fire
Alarm Control Panel via an analog circuit (SLC) over a
single pair of wires.
The device shall provide dry contacts and positive feed-
back of the controlled equipment’s status annunciating
upon activation. It shall be Gamewell-FCI RCE-95.
Specifications
Input Power: 24 VDC from analog circuit
Standby Current: 0.0008A
Alarm Current: 0.0015A
Operating
Temperature: 32°F to 120°F (0°C to 49°C)
Relative Humidity: 93% non-condensing
Fuse: 2 amp Slo Blow
Contact Rating: 2.0 amp at 30 VDC
0.2 amp at 120 VAC
Dimensions: 4.688" (11.908 cm) backbox
Ordering Information
Part NumberDescription
RCE-95 Relay control element device. XP95
protocol compatible.
70839 Trim ring for flush mounting the RCE-95.
RCD Optional relay control display; provides
annunciation of the RCE-95 control ele-
ment devices at the FACP. One needed for
every eight RCEs.
Note: The Relay Control Display (RCD) is only compatible
with the IF632 and IF650 FACPs.