GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60532 Rev. B page 2 of 3
www.gamewell-fci.com
Description (Continued)
The RTS2 and RTS2-AOS multi-signaling accessories are
designed to operate with the InnovairFlex 4-wire conven-
tional duct smoke detectors. These accessories include a
key switch that can be used to select one of two connected
sensors to be tested, reset, or both by pressing a push
button switch. They also enable sensitivity measurements
using the SENS-RDR sensitivity reader (sold separately).
The AOS (Add-On Strobe) is an optional accessory
included with the RTS2-AOS model.
Specifications, Duct Smoke Detector
Accessories
APA151 Piezo Annunciator
Voltage: Regulated 24 VDC
Operating Voltage: 16 to 33 VDC
Maximum Alarm Current: 30 mA
Temperature Range: 0°C to 49°C (32°F to 120°F)
Relative Humidity: 10 to 93% non-condensing
Wire Gauge: 12 to 18 AWG
Dimensions: 4.6” H × 2.9” W × .45” D
(11.6 H x 7.3 W x 1.1 D cm)
MHR/MHW SpectrAlert® Advance Mini-Horns
Voltage: Regulated 12 DC or FWR
(Full Wave Rectified) or
Regulated 24 VDC or FWR
Operating Voltage: 8 to 33 VDC (9 to 33 VDC
with Sync•Circuit™ Module)
Sounder Current Draw: 22 mA RMS max.
at 8 to 17.5 Volts DC
17 mA RMS max.
at 8 to 17.5 Volts FWR
29 mA RMS max.
at 16 to 33 Volts DC
25 mA RMS max.
at 16 to 33 Volts FWR
Temperature Range: 0°C to 49°C (32°F to 120°F)
Humidity Range 10 to 93% non-condensing
Nominal Sounder
Frequency: 3 kHz
Wire Gauge: 12 to 18 AWG
Dimensions 4.6” H × 2.9” W × 0.45” D
(11.6 H x 7.3 W x 1.1 D cm)
RA100Z/RA100ZA Remote Annunciator
Voltage Range: Conventional System: 3.1 to
32 VDC Intelligent System:
18 to 32 VDC
Maximum Alarm Current: 12 mA
Dimensions: 4.6” H × 2.8” W × 1.3” D
(11.6 H x 7.1 W x 3.3 D cm)
Specifications, Duct Smoke Detector
Accessories (Continued)
RTS151 Remote Test Station
Power Requirements: Alarm LED: 2.8 to 32 VDC,
12 mA max.
Total Current: 105 mA max.
Test Switch: 10 VA @ 32 VDC
Reset Switch: 10 VA @ 32 VDC
Alarm Response Time: 40 seconds max.
Temperature Range: –10°C to 60°C
(14°F to 140°F)
Relative Humidity: 95% non-condensing
Wire Gauge: 14 to 18 AWG
Dimensions: 4.8” H x 2.90” W x 1.4” D
(12.1 H x 7.3 W x 3.5 D cm)
RTS151KEY Remote Test Station with Key
Power Requirements: Power LED (Green): 14 to
35 VDC, 12 mA max.
Alarm LED (Red): 2.8 to 32
VDC, 12 mA max.
Total Current: 105 mA max.
Alarm Response Time: 40 seconds max.
Temperature Range: –10°C to 60°C
(14°F to 140°F)
Relative Humidity: 95% non-condensing
Wire Gauge: 14 to 18 AWG
Dimensions 4.6” H × 2.75” W × 1.8” D
(11.6 H x 6.9 W x 4.5 D cm)
RTS2 and RTS2-AOS Multi-signaling Accessory
Voltage: 20 to 29 VDC
Power Requirements:
Standby: 3.0 mA max.
Trouble: 16.0 mA max.
Alarm without strobe: 30 mA max.
Alarm with strobe: 55 mA max.
Sounder: 85 dBA at ten feet
Temperature Range: –10°C to 60°C
(14°F to 140°F)
Relative Humidity: 95% non-condensing
Wire Gauge: 14 to 22 AWG
Dimensions: 4.8” W x 5.3” H x 1.6” D
(12.1 W x 13.4 H x 4.0 D cm)
For information on the most recent product specifications
and listing information, prefer to the Gamewell-FCI Web