Vigilon Plus fire alarm system
How to use the integral printer
Assuming the panel has an integral printer:
To Switch On / Off the Printer
a. Press the MENU ON/OFF button.
b. Press the F1 button to select [Control].
c. Press the F3 button to select [Printer]. Check that ‘Printer
appears on the screen.
d. Press the F3 button to select [On] / [Off] and then press the
F2 button to select [Enter]. ‘Printer is on/off’ is displayed.
To action a Paper Feed
a. Press the MENU ON/OFF button.
b. Press the F1 button to select [Control].
c. Press the F3 button to select [Printer]. Check that ‘Printer
appears on the screen.
d. Press the F2 button to select [Paper Fd]. Note the display
and menu prompts are cleared. Printer performs 8 line feeds.
To conduct a Printer Test
a. Press the MENU ON/OFF button.
b. Press the F1 button to select [Control].
c. Press the F3 button to select [Printer]. Check that ‘Printer
appears on the screen.
d. Press the F1 button to select [Test]. Note the display and
menu prompts are cleared.
e. Check that the printer provides a listing of all the characters it
is capable of printing.
How to enable/disable Sensing
NA
These operations are not applicable for a Vigilon Plus
Network Node.
It is only possible to disable a Manual
Call Point (MCP) individually, not as part
of a range. DISABLING A MCP IS NOT
RECOMMENDED.
A sensing device such as a sensor or MCP in the system
can be disabled/enabled. You will need the device and loop
numbers, this information can be found in the site specic
documents held by the person responsible for the re system.
a. Press the MENU ON/OFF button.
b. Press the F1 button to select [Control].
c. Press the F4 button to select [UserCode]. At the ashing
cursor using and the keypad input your PIN code and then
press the Enter button.
d. To disable a device: Press the F2 button to select
[Disable]. To enable a device: Press the F1 button to
select [Enable]. The display shows either ‘Enable’ or ‘Disable’.
e. Press the F1 button to select [Sensing]. Notice ‘Device’
followed by a ashing cursor appears on the display. Use
the keypad to input a device number from a range 1 to 200).
f. Press the F2 button to select [Loop]. Notice ‘Loop’
followed by a ashing cursor on the display. Use the
keypad to input a loop number from a range 1 to 6.
g. Press the F2 button to select [Enter]. This is conrmed
by: ‘Device(s) enabled’ or ‘Device(s) disabled’. The
Disablement light is lit upon disablement of the device.