Fire Panels Indications given of various conditions
4188-424 issue 8_Part 2_07-14_Xenex 6
Indications given of various conditions
CONDITIONS
Normal Fire New fire
(different
zone)
Access
level 2, 3
or 4
Function
key
pressed
Visual
Zone Fire (1-8) - Red ON ON
Fire Common - Red ON ON
Disabled - Yellow
Test - Yellow
Power - Green ON ON ON ON ON
Access / Function - Yellow ON Fast pulse
Audible
Buzzer ON ON
Sounder circuits ON ON
Signal
Out
Aux Relay contacts Normally de-energised normal C/O C/O normal normal
Common fault -
Normally active active active active active active
Common fire- Normally deactive de active active active de active de active
C/O - Change Over
Fault Conditions
In the event of an automatic fault detection the indications given are:
q Common Fault light is lit and may be accompanied with other fault indicators
q buzzer sounds intermittent, (except for system fault which is a continuous sound).
To Cancel the fault buzzer
a)
#Enter the 3 digit code to gain access to the controls.
# Coded entry is only required if Cancel Buzzer function is configured for operation at Access level 2.
b)b)
After investigating fault, press the Cancel Buzzer button. Notice the buzzer is silenced but other
indications remain active.
The fault indications are normally automatically extinguished once the fault condition has been rectified.
Action to rectify fault
NOTE: All fault rectification work must be done by suitably qualified personnel.
q The fault indicators may be extinguished during a fire condition.
q The mains failure condition overrides all other fault indications in order to preserve battery standby capacity.
NOTE: A comprehensive fault finding guide is included in the Data Installation and Commissioning guide.