Fault Conditions Fire Panels
7 4188-424 issue 8_Part 2_07-14_Xenex
Other Access level 2 operations
To carry out a display test
q
Enter the 3 digit code to gain access to the controls.
- Coded entry is only required if Display test function is configured for operation at Access level 2.
q Press the ‘shift‘ button and then the display button.
- Ensure that all the LEDs light in sequence and the buzzer sounds.
How to set the panel to operate in Test mode A
Selecting Test mode A will cause triggered manual call point or fire detector in the test zone to give Fire
indication for 10 seconds duration followed by a system reset.
q Enter the 3 digit code to gain access to the controls. Check that the Access/function lamp is lit.
q Press the and 3 buttons followed by the number of the zone to be placed in test mode.
- Check that the Test indicator is On and the respective zone fault indicator is lit.
- The zone can now be tested without an alarm of fire.
How to exit from Access level 2 to Access level 1
q Press the and 0 buttons.- Check that the Access/function lamp is extinguished. The panel is now at
access level AL1.
How to set the panel to operate in Test mode B
Selecting Test mode B will cause triggered manual call point or fire detector in the test zone to give System
alarms for the first 2 seconds and at the same time a Fire indication for 10 seconds duration followed by a
system reset.
q Enter the 3 digit code to gain access to the controls. Check that the Access/function lamp is lit.
q Press the and 4 buttons followed by the number of the zone to be placed in test mode.
- Check that the Test indicator is On and the respective zone fault indicator is lit.
- The zone can now be tested with 2 seconds alarm of fire.
How to cancel Test mode A/B operation
Selecting cancel Test mode A/B will cause the selected zone to operate normally.
q
Enter the 3 digit code to gain access to the controls. Check that the Access/function lamp is lit.
q
Press the and 5 buttons followed by the number of the zone to have test mode cleared.
- The test mode A or B is cancelled.