NFPA Standard-Specific Requirements
The following figure illustrates an example of Central Station/Remote Station Reporting using a 411UD. The relay contacts from the
GF505/GF510 may be used to trip any dialer UL listed for Central Station/Remote Station Reporting Services.
411UD FACP
Alarm TB2-1 TB8-1
TB2-2 TB8-3
Trouble TB2-3 TB8-4
TB2-4 TB8-6
Supervisory TB2-5 TB8-7
TB2-6 TB8-9
Table B.1 411UD Connections to FACP
Figure B.1 GF505/GF510 FACP Connection to 411UD
Channel1
Channel 2
Channel 3
Channel 4 (2.2K ELR)
Relay Output (DACT Trouble) from 411UD
FACP Supervisory Relay
FACP Alarm Relay
FACP Trouble Relay
J4 Not Installed
411UD
1
2
3
4
5
6
7
8
+ 24 VDC nonresettable power
- 24 VDC nonresettable power
2.2K ELRs P/N 27070
1
2
3
4
5
6
7
8
9
1 2 3 4 5 6 7
FACP
Jumper -VDC to Trouble Relay contact
Trouble Input
(non-supervised,
power-limited)
GF505 & GF510 Manual P/N 53164:B5 6/12/2018
109