EasyManua.ls Logo

Honeywell GSMV4G - Zone Trigger Mode; 4204 Mode and Two-4204 Mode; Supervision Features

Honeywell GSMV4G
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 1: General Information
1-3
Zone Trigger Mode
This mode is for use with control panels that do not support ECP communication nor 4204
Relay Modules
The communicator provides six input zones
Each zone can be configured for +V, V, or EOLR triggering
UL: For the communicator, only the V+ inverted, V– non-inverted, and EOL options have
been evaluated.
Each zone can be programmed for inverted operation, delayed reporting, and restoral
reporting
Zone 1 input can distinguish between pulsed and steady signals and report fire or
burglary alarms respectively
Zone 1 can also be programmed to report LYNX panic (if used with LYNX control)
UL: This feature has not been evaluated by UL.
Reports are sent in ADEMCO High-Speed format
UL
Opening and Closing ring back is supported by the control panel’s digital dialer.
4204 Mode and Two-4204 Mode
This mode is for use with Honeywell control panels that do not support ECP communica-
tion, but do support 4204 Relay Modules
The communicator connects to the control panel’s keypad terminals
The control panel treats the communicator as 4204 Relay Module(s), so program the
control panel accordingly, including setting the communicator’s proper 4204 device
address
4204 mode provides up to four zone inputs, plus two optional trigger zones, depending on
options programmed
Two-4204 mode provides up to eight zone inputs, depending on options programmed
Each 4204 zone can be programmed for delayed reporting and restoral reporting
Reports are sent in ADEMCO High-Speed format
UL
Opening and Closing ring back is supported by the control panel’s digital dialer.
4204 Mode and Two-4204 Mode has not been evaluated by UL.
Supervision Features
The communicator provides the following types of supervision and communicator fault
detection:
Network communication failure
: In the event the AlarmNet network does not hear a
supervisory message from the communicator within a specified time (“Supervision” option,
24 hours, 30 days, or none), AlarmNet notifies the central station of a communication
failure.
Communication path failure
: In the event the module detects a communication path
failure, both the Central Station and the control panel can be notified of the trouble
condition. The failure is considered a true fault when the fault time has expired ("GSM
Fault Time" option) provided it has been set to a non-zero value. Notification is sent to
the central station upon this expiration.

Table of Contents

Other manuals for Honeywell GSMV4G

Related product manuals