5 Specications
Input power: 100-240 VAC, 50/60 Hz
24 VDC
DC output power: 15 watts (internal supply) or
50 watts (internal supply)
Relay output rating: 5A, 28 VDC or 250 VAC (resistive load)
Optional relay output rating 5A, 28 VDC or 250 VAC (resistive load)
Optional milliamp loop
output
10 bit 4-20mA output. Maximum load 750 ohms
with nominal 24 Vdc
Communication: RS232 Modbus
Length of communication
lines:
Operating environment: Industrial
Operating temperature
range:
-25 to 50ºC (-13ºF to 122ºF)
Operating humidity range: 0 to 90% RH non-condensing
Operating altitude: 2000m (6562 ft)
Audible alarm: 100 dB
Display: 128 x 64, backlight graphic LCD
Visual Indicators: 6 LED status indicators
Pollution degree: N4: 3
Enclosure (N4): NEMA 4X, Div. 2, Groups A,B,C,D, Category II
Enclosure (XP): NEMA 7, Div. 1 & 2, Groups B,C,D
Dimensions (H x W x D): N4: 10.32” x 8.92” x 3.17” (23.62 x 22.66 x 8.05cm)
XP: 15.10” x 13” x 6.25” (36.2 x 33 x 15.88cm)
Enclosure NEMA 4 painted carbon steel
Enclosure NEMA4X SS316
Enclosure NEMA4X Polycarbonate
Weight: N4: 2.27 Kg XP: 18.14 Kg
Certifications: CSA C22.2 No. 1010-1, ISA S82.02
CSA C22.2 No 152 (for combustibles using mA
input)
UL 1604/C22.2 No. 213 (NEMA 4X = Div 2, Gr A,
B, C, D; NEMA 7 = Div 1, Gr , B, C, D
EN55011 & EN61000 (CE mark))