180 HC900 Process & Safety Controller User and Installation Manual Revision 6
21 April 2017
Number
of Red
Strobes
Possible Causes
Lead and/or Reserve Controller
Action(s)
User Action
Honeywell OI
Indication
HCDesigner/HC
Utilities Indication
6
High temperature
condition in a Scanner
2 rack has been
detected.
1. Associated AI blocks that are
configured as T/Cs set their fail pin
on, their warn pin off, and their
output pin to the failsafe value.
2. Associated AI blocks that are
configured as T/Cs set their IO
status to either:
CJ High Temperature if one of
the two CJs on an AI card is
indicating a temperature greater
than 70 degrees C
CJ Failure if both CJ sensors are
failing to convert.
3. Associated rack monitor blocks
module fail pin is turned on.
4. Associated rack monitor blocks
RACK OK pin is turned off.
5. Associated rack monitor blocks
HITEMP pin is turned on.
6. ASYS and FSYS blocks HITEMP
pins are turned on.
7. ASYS and FSYS blocks HW OK
pins are turned off.
6
Scanner 2 has a CPU
or Memory diagnostic.
1. Associated rack monitor blocks
RACK OK pin is turned off.
2. ASYS and FSYS blocks HW
OK pins are turned off.
See CPU or
MEMORY in the
associated racks
Rack Diagnostics
Overview display.
See CPU or
Memory in Rack
Diagnostics
dialog box.
7
A Scanner 2 rack has
a bad power supply.
1. Associated rack monitor blocks
RACK OK pin is turned off.
2. ASYS and FSYS blocks HW
OK pins are turned off.
Locate the Scanner 2 that indicates a
bad power-supply diagnostic, and
replace the defective supply.
See POWER
SUPPLY
DIAGNOSTICS in
the associated
rack’s Rack
Diagnostics
Overview display.
See Power
Supply
Diagnostics in
Rack
Diagnostics
dialog box.