Revision 6 HC900 Process & Safety Controller User and Installation Manual 219
21 April 2017
8 Point Analog Input
Step
Action
3
Set DIP switch positions SW1 through SW8.
Set each input’s DIP switch positions according to the input type. For Input n use Switch n. For example, for
Input 1 use Switch 1, for Input 2 use Switch 2, etc. If an input is not used, set its DIP switch positions to OFF.
SW9
Volt, millivolt:
1 2
O
N
1 2
O
N
1 2
O
N
Ohms:
1 2
O
N
1 2
O
N
1 2
O
N
:
1 2
O
N
1 2
O
N
1 2
O
N
1 2
O
N
RTD:
1 2
O
N
1 2
O
N
1 2
O
N
Transmitter
SW9 is the red power switch for 24 volt supply. Module RIUP is not affected by using the RTP.
See page 224 for RTP internal schematic.
Fuses: 80mA Time lag
Littelfuse part #
37400800410
UL/CSA approved
Transmitter:
Loop Powered
Externally Powered
Milliamp: