Installation
2/03 10260A Series Actuators – Installation, Operations, and Maintenance 21
3.4 Electrical Installation
3.4.1 General Wiring Recommendations
WARNING
!
Wiring should be performed by qualified personnel only.
Wiring must conform to national and local electrical codes.
In general, stranded copper wire should be used. Unless locally applicable codes dictate otherwise, the
recommended minimum wire sizes in Table 3-1 should be observed.
Table 3-1 Recommended Minimum Wire Size
Gage No. Description
14 Earth ground wire to common power supply.
18 Earth ground wire to single actuator. 120/240 V ac line leads. +24 V and common
signal leads.
Safety Precautions
WARNING
!
An external disconnect switch must be installed to break all current carrying conductors. Turn off power
before working on conductors. Failure to observe this precaution may result in serious personal injury.