Calibration Procedures
2/03 10260A Series Actuators – Installation, Operations, and Maintenance 31
4. Once the cams are set in the correct positions, turn the locking nut clockwise until snug tight (it does
not have to be “hard” tight and does not have to completely flatten the spring washer).
5. Double check limit switch actuation by first manually driving the actuator to each end of travel and
hearing the switch click or by detecting it with a continuity tester. Secondly, drive the actuator to both
ends of travel (using the auto/manual switch or by providing minimum and full input signal) and make
sure the switches activate.
CAM 1 (REF)
SWITCH 1
SWITCH 3
SWITCH 5
NOTE: Switches 2, 4 and 6
are located on left side.
CAM
SLOTS
LOCKING
NUT
Figure 4-1 Location of Auxiliary Switches