EasyManua.ls Logo

Honeywell HercuLine 10260A - Actuator Does Not Control to the Proper Position; Table 9-5 Troubleshooting Control Action on Actuator

Honeywell HercuLine 10260A
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
2/03 10260A Series Actuators – Installation, Operations, and Maintenance 73
9.2.4 Actuator does not control to the proper position.
Table 9-5 explains how to troubleshoot the actuator for the correct control operation.
Table 9-5 Troubleshooting Control Action on Actuator
Step What to Do How To Do it or Where to Find the Instructions
1
Check the connectors to the Motor
Positioner Board.
Check to make sure connectors are securely
seated in headers on Motor Position board. See
Figure 4-5.
2
Check that cables are plugged into the
correct headers on NCS output board.
Check to make sure connector is seated in header
J4 on NCS board. See Figure 4-6.
3
Check NCS Output signal. On NCS Output Card, using a DVM, check that
the voltage across the pins of W11 (Figure 4-4) is
in the range of 0 to 1.25 Vdc. Check that voltage
is increasing for CCW operation and decreasing
for CW operation.
4
Check input signal. Using a DVM verify that the input signal at TB-30
to 31 (Figure 3-11) is in the range of 1 Vdc to 5
Vdc. If not check for the dropping resistor.
5
Check CW/CCW jumper Upon change of input signal, if actuator travels to
0 % or 100 % check to make sure CW/CCW
switch and jumper (Figure 4-6) are in correct
positions.
6
Check/Recalibrate Refer to Section 4 to recalibrate actuator. First
check Section 4.6 for proper positioning and
calibration of Non-contact Position Sensor.
7
Replace CAT/PAT Board. Refer to the replacement procedure in Section 8 –
Replacement/Recommended Spare Parts.

Table of Contents

Related product manuals