EasyManua.ls Logo

Honeywell HercuLine 10260A - Auto;Manual Switch Does Not Operate Correctly; Table 9-6 Troubleshooting the Auto;Manual Switch

Honeywell HercuLine 10260A
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10260A Series Actuators Installation, Operations, and Maintenance Manual
74 10260A Series Actuators – Installation, Operations, and Maintenance 2/03
9.2.5 Auto/Manual Switch does not operate correctly.
Table 9-6 explains how to troubleshoot the actuator Auto/Manual Switch.
Table 9-6 Troubleshooting the Auto /Manual Switch
Step What to Do How To Do it or Where to Find the Instructions
1
Check the Auto/Manual Switch in
Manual Mode (CCW).
Set the Auto/Manual Switch in the CCW position.
Verify that shaft turns CCW (viewed from shaft
end of actuator).
2
Check the Auto/Manual Switch in
Manual Mode (CW).
Set the Auto/Manual Switch in the CW position.
Verify that shaft turns CW (viewed from shaft end
of actuator).
3
Check the Auto/Manual Switch in Auto
Mode.
Set the Auto/Manual Switch in the Auto position.
Using the controller, drive the unit CCW and CW.
4
Replace the controller. Refer to the replacement procedure in Section 8 –
Replacement/Recommended Spare Parts. Or if
an external controller is being used refer to it’s
Operators Manual.

Table of Contents

Related product manuals