Basicsforinstallingthedeviceinapipe
UsermanualforHONR100gaspressureregulatorwithHONP095NGpilot 29
4.3 Operatingandmeasuringlines
Thelinesmustbearrangedandsizedinsuchawaythatthedevices’intendedfunctionwillbe
ensured.
Measuringline
Themeasuringlinetransmitsthepressureprocessvaluefromthesensing
pointtothemeasuringdiaphragmofacontrollerorthepilotofagaspressure
regulatororsafetyreliefvalveortothemeasuringdiaphragmofthemoni‐
toringdeviceofaslam‐shutdevice.Itneedstobeconnectedtothepipe
sidewaysorupwardsseparatelyforeachdevice.Inthecaseofsafetyequip‐
ment,themeasuringlinemustbeconnectedupstreamofthefirstoutlet‐side
shut‐offdeviceinsuchawaythatitcannotbeshutoff.Ifthemeasuringlineis
additionallyconnecteddownstreamofthefirstoutlet‐sideshut‐offdevice,
3‐wayballvalveswithnegativeoverlapmustbeusedforswitching.Theseball
valvesdonothaveavalvepositioninwhichbothmeasuringlinescanbefully
closedatthesametime.
Ventline
Theventlineisusedtoconnectameasuringdiaphragmtotheatmosphere.If
themeasuringunitbecomesdamaged(e.g., diaphragmrupture),itcanstart
conveyinggas.Undercertainoperatingconditions,andfollowingconsultation
withthemanufacturer,ventlinescanbeomittedifventvalves(HON 915)or
safetydiaphragmconfigurationscanbeusedinstead.
Blowdownline
Theblowdownlineinasafetyreliefvalveisusedtodivertgas(leakinggas,
for example)intotheatmosphere.
Groupingventlinesorblowdownlines(intoaheader)ispermissibleifitdoesnothavea
negativeimpactontheindividualdevices’operation.Withinthiscontext,itisrecommended
tohavethecross‐sectionalareaoftheheaderbeatleastfivetimesaslargeasthetotalofthe
individuallines’cross‐sectionalareas.
Forprimaryslam‐shutdevices,itisrecommendedtoroutetheslam‐shutdevices’ventlines
separately.Ventlinesmustnotbegroupedtogetherwithblowdownlines.
Dischargingline
Whenusingindirectacting(pilot‐operated)slam‐shutdevices,thedischarg‐
inglineisusedtodiverttheexhaustgasfromthepilotintothesystemsout‐
letchamber.Oncertaindevices,thedischarginglinewillbegroupedwiththe
feedbackline.
Feedbackline
Whenusingindirectacting(pilot‐operated)slam‐shutdevices,
thefeedback
lineisusedtoreturntheoutletpressuretotheactuator.
Connectionlinesbetween
deviceandgasregulating
line