Transport,installationandstart‐up
UsermanualforHONR100gaspressureregulatorwithHONP095NGpilot 34
5.2 Installingthegaspressureregulator
Preparethefollowingmaterials:
Flangegaskets
Threadedbolts
Washers
Nuts
Thequantityandsizearedependentonthefollowingcriteria:
Designandsizeoftheflange
Assesstheinstallationsituation.
Thenumbershavethefollowingmeaning:
Figure No. Meaning
1 Gasregulatinglineinlet
2 Studsandwashers
3 Flangegasket
4 Nutsandwashers
5 Gasregulatinglineoutlet
Proceedasfollows:
Figure Step Description
1
Removetheprotectiveplatesfromthe
flange.
2
Transportthedevicetothelocationwhere
itwillbeinstalled.
Thedeviceneedstobeinstalledinthe
pipinginahorizontalandlevelposition.
Ifyouwanttouseadifferentinstallation
position,consultwiththemanufacturer
first.
Payattentiontothedirectionofflowfor
thegaseousfluidasmarkedonthe
body.
3
Secureandsupportthedevice’spositionin
suchawaythatthedevicecanbeinstalled
inthepipingwithoutanystressandthat
thepipingsweightwillbesupportedas
well.
4 Installtheflangegaskets.
5
Screwdowntheflangecrosswiseinthe
specifiedorder.Whendoingso,makesure
toobservethetorquesspecifiedbythe
flangegaskets’manufacturer.
Preparingthematerials
Assessingthesituation
Mountingtheactuator
assembly

Table of Contents