Maintenance
UsermanualforHONR100gaspressureregulatorwithHONP095NGpilot 46
Schematicdiagram:
Thenumbershavethefollowingmeaning:
No. Meaning
1 Inletstopvalvearmature
2 Inletpressuregauge
3 Gaspressureregulator
4 Loadingpressuregauge
5 Blowdownlineshut‐offdevice
6 Outletpressuregauge
7 Outletstopvalvearmature
Proceedasfollows:
Step Description
1 Closetheinletvalve(1).
2 Closetheoutletvalve(7).
3
Depressurizethepilot.
Turnthesetscrewonthepilotclockwiseuntilthepressureintheregulatorisequalized.
4
Opentheblowdownline’s(5)shut‐offdevicetodischargethepressurebetweentheinlet
andtheoutlet.
Allthegaspressureregulator’slinesmustbepurgedwithnitrogenbeforethedeviceisre‐
moved.