Maintenance
UsermanualforHONR100gaspressureregulatorwithHONP095NGpilot 56
Figure Step Description
19
Takethecompensatingplate.Replacethe
O‐ring(2)withanew,greasedO‐ring.
Checktheslidingring(1)fordamage.
Replaceitifnecessary.
20
Slidethecompensatingplateontothe
valveshankallthewaytothestop.Im‐
portant!Makesurenottodamagethe
O‐ring(1)orchangeitsposition.Makesure
thatthecompensatingplateispositioned
correctly.Theslidingring(2)shouldbeon
topandtheO‐ring(3)underneathit.
21
Securethecompensatingplatewithanew
retainingring(1).
22
Insertthevalveshank(1)backintothe
actuatorassemblyfromabove.The
compensatingplateshouldsittightlyinside
theupperpartoftheguidebush(2).
23
Takethevalveplate.Checkthesealing
edgefordamage.Thesealingedgemust
nothaveanyscratchesordents.Ifneces‐
sary,replacethevalveplatewithanew
one.