INTELLIGUARD 9000™
74-3047—118
NOTE: Onl
one
round connection is re
uired between the
I9000 CU and each RIPS for
round reference
this
can be throu
h the earth
round connection
. Avoid
round loops.
5.
When installation is complete and power is applied,
learn the ISPs in the RIPS.
NOTE: Steps 5 a. throu
h 5
. ma
be replaced b
usin
the
PRO 9000 software. See the Commission section,
steps 1a. throu
h 1c. for more information.
a. Make sure the LED DS1 on each installed ISP
RIPS
in enabled, see the followin
notes.
b. From the CC2, select
CONFIGURATION
from the
MODE menu.
c. From the CC2, select
LEARNING
MODE.
d. From the CC2, select
1-DEVICES WITH ADDRESS
SWITCHES
. The CC2 displa
s
Searching
. The
LED DS1 on each installed ISP flashes as it is
learned.
e. The CU polls all address t
pe devices and when
the
have all been learned, the CU automaticall
displa
s
DEVICES = #
, where
#
is the total number
of devices known b
the s
stem includin
ISPs.
f. The LED DS1 on each installed ISP flashes each
time the device is polled b
the CU.
. From the CC2, exit from the CONFIGURATION
menu for chan
es to become effective.
NOTES:
— The RIPS have two auxiliar
power outputs. Each
output supplies 12.8 Vdc nominal with a current
limited to 400 mA.
— The ISP data LED is active when TB3 pins 3 and
4 are shorted
tamper is active, cover open
.
Fig. 18. ISP wiring, configuration.
1234 1234 1234 1234 1234
TB1 TB2 TB3 TB4 TB5
4
1
R21
DS
XA1
S1
S1
ON
1
2
3
4
ADDRESS
SELECTION
NOT USED
OUTPUT MODE
SWITCHES SHOWN IN
OFF POSITION
1
2
S1
ON
OFF
1
2
S1
ON
OFF
1
2
S1
ON
OFF
1
2
S1
ON
OFF
0123
ISP ADDRESS
4
S1
ON
OFF
4
S1
ON
OFF
PULSATING STEADY
OUTPUT MODE
AC ON
GROUND
BATT. 1 & 2 -
BATTERY 1 +
BATTERY 2 +
AC
AC
COMMON -
22V +
OUTPUT -
OUTPUT +
TAMPER -
TAMPER +
VX1 -
VX1 +
TxRx -
TxRx +
VX2 -
VX2 +
12V
7 Ah
16V
37 VA
GIM
1A
12V
0.4A
12V
0.4A
RS-485
COM 1 OR COM 2
J1
DS1 = Tx DATA
M16079B
LEVER
1
EXCEEDING 400 mA ON EITHER VX1 OR VX2 WILL CAUSE THE OUTPUT TO SHUT
DOWN UNTIL THE CAUSE OF OVERLOAD IS REMOVED.
1
2
1