BCU 580 · Edition 11.15l 120
BCM 500
15.4 Installation
Installation position: vertically upright, horizontal or
tilted to the left or right.
The BCM mounting is designed for horizontally aligned
35 × 7.5 mm DIN rails.
G1
G2
G3
XXX ADR
G1
G2
G3
XXX ADR
G1
G2
G3
XXX ADR
If the DIN rail is aligned vertically, end clamps are re-
quired (e.g. Clipfix 35 by Phoenix Contact) to prevent
the control unit from slipping.
Install in a clean environment (e.g. a control cabinet)
with an enclosure ≥ IP 54, whereby no condensation is
permitted.
15.5 Selection
Code Description
BCM Bus module
500 Series 500
S0 Standard communication
B2 Profinet
/3 Two RJ45 sockets
3 Three-point step control via bus
Order No.: 74960663
15.6 Technical data
Electrical data
Power consumption: 1.2 VA.
Power loss: 0.7 W.
Mechanical data
Dimensions (W × H × D):
32.5 × 115 × 100 mm.
Weight: 0.3 kg.
Environment
Ambient temperature:
20 to +60°C (4 to +14F).
Storage temperature:
20 to +60°C (4 to +14F).
Climate: no condensation permitted.
Enclosure: IP 20 pursuant to IEC 529.
Installation location: min. IP 54 (for installation in a
control cabinet).