BCU 480 · Edition 03.16l 48
Parameters
4.7 Air valve control on BCU..L
Parameter 30, Behaviour of the air valve during opera-
tion.
Parameter 31, Behaviour of the air valve during start-up.
Parameter 32, Behaviour of the air valve in the event of
a fault lock-out.
The BCU..L features an adjustable air valve control. The
display shows that purging is currently being carried
out with
P 0
.
A
indicates that the air valve is being ac-
tivated for cooling or heating.
The BCU..L supports the following functions:
– Purge
Cooling in start-up position/standby
Switching of the burner between low and high burner
capacity during operation via the air valve
To start up the burner as intended, external activation
of the air valve can be blocked during start-up (pre-
vents synchronization problems between the BCU
and the central control system).
Setting the air valve parameters, so that it
– opens with valve V1
– opens with valve V2
opens once the main burner has reached its operat-
ing position
Low fire over-run time t
KN
after a controlled shut-
down
4.7. 1 Purge
In the case of multiple burner applications, burners with
mechanical combustion air supply are used. The air for
combustion and pre-purge is supplied by a central fan
controlled by a separate logic. This logic determines the
purging time.
The BCU..L..E1 with adapted power management sup-
ports centrally-controlled pre-purge or post-purge.
The BCU..L is informed that purging is currently being
performed by input 22. It then opens the air valve, re-
gardless of the status of the other inputs (purging has
priority). The display indicates
P 0
.
On BCUs without power management, input 22 and in-
put 5 (safety interlocks) must be activated for purging,
see connection diagrams on pages 14 (BCU 480), 16
(BCU 480..B1) and 18 (BCU 480..P with industrial plug
connector).
4.7. 2 Cooling in start-up position/standby
The air valve can be activated externally via input 23 for
cooling in the start-up position. During activation of the
air valve the display shows
A 0
, indicating that cooling is
currently being carried out.
4.7.3 Burner start
Parameters 30 and 31 determine the behaviour of the
air valve during burner start.