Project planning information
6.18 Third gas valve (can be
shut down) on BCU..L
Units with air valve control have an
additional contact (terminal), which
closes at the same time as the air
valve.
This can be used to activate a third
gas valve (V3). To do this, the output
of valve V1 or V2 must be used as
auxiliary energy (as a result of the
required flame control).
13
N
14 15
50 51
V3 V2
The opposite application describes
a two-stage-controlled burner
without a pneumatic air/gas ratio
control system. The third gas valve
(V3) and the air valve are activated
simultaneously. During purging/
cooling, the gas valve (V3) is not
activated.