The Receiver box button LED
is green but the boiler does
not switch on.
Boiler wiring might be incorrect or
broken
Check the Receiver box wiring
The status LED on the
Receiver box is red
(Communication loss)
The Receiver box receives no
communication from the
thermostat: RF communication
might be too far or is blocked due to
Receiver box location.
Thermostat is no longer powered.
Try to move thermostat or Receiver box closer or
re-locate.
Check the power to the thermostat
Thermostat alert messages
The Wi-Fi radio of thermostat is
faulty.
The internal memory of thermostat
is faulty.
INDOOR TEMPERATURE SENSOR
ERROR
(wired only) The external
temperature sensor is not
connected or the wiring is faulty.
Check external sensor wiring and sensor
The thermostat receives no
communication from the
thermostat: RF signal is blocked due
to the location of the thermostat.
Receiver box is no longer powered.
RF communication might be too far or is blocked
due to the location of the Thermostat or Receiver
box.
Check the power to the Receiver box
There is a weak radio signal from the
Receiver box
Try to move thermostat or Receiver box closer or
re-locate.
The thermostat is not bound with
the Receiver box
Bind or re-bind the Receiver box
Thermostat has no longer Internet
connection.
End user needs to check their Internet connection
via router.
Thermostat has no longer a Wi-Fi
connection.
End user needs to check their Wi-Fi network of
router.
Thermostat is connected to Internet
but not yet registered to an account.
End user needs to download the App, create an
account and register the thermostat.
Thermostat is not connected to
Wi-Fi network.
End user needs to download the App, create an
account, connect and register the thermostat.
The OpenTherm boiler reported a
failure number XX.
BOILER LOW WATER PRESSURE
The boiler reported low water
pressure.
Fill up the hydronic system with water.