EasyManua.ls Logo

Honeywell MagneW 3000 Plus - Electrical Connection Details; Electrical Connection Considerations; Cable Length and Grounding

Honeywell MagneW 3000 Plus
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 MagneW 3000
PLUS
Specification and Application Guide 1/98
Electrical Connection Considerations
For electrical connections of the
converter/detector the following should
be checked:
Cable types
Laying of cables
Cable lengths
Grounding
Cable Types
The standard cables for the instrument
are as follows:
Signal cable:
2-core individually
double-shielded cable
Excitation cable:
2-core chloroprene
cabtyre cable
If standard cables are unavailable,
contact Honeywell for
recommendations.
Laying of Cables
Do not lay the cables near a motor, a
transformer, or a large-current cable
which may cause induction noise.
Lay the cables 1 meter (3.3 feet) or
more away from heavy-duty power
cables.
Lay the signal cable in a metallic
conduit, a flexible tube, or a duct,
separately from the excitation current
cable or any other power cables.
Wire with electrical tube and duct to
keep out water and protect the wire
from external damage. Lay the tube
so that no water gets into the unit.
Use a waterproof gland at the conduit
connection.
Do not employ any junction point for
connection of the signal cable or the
exciting cable between the detector
and the converter. When it is
unavoidable to employ a junction
point, use Cable Junction Box (Part
No. 80720002-000) which has been
designed specifically for this
purpose.
Do not short the excitation current
terminals X and Y of the converter.
Cable Lengths
The length of the cable between the
detector and the converter depends
on the electrical conductivity (µS/m)
of the fluid to be measured. (Refer to
Figure 9 on page 10.)
In general, the electrical conductivity
of potable water or sewage water is of
a level of 10000 µS/m (100 µΩ/cm).
Therefore, for a detector of 15 mm
(0.6 in.) diameter or over, the
maximum allowable cable length is
300 meters (984 feet).
Signal Cable
If a signal cable is required to be laid
more than 500 meters (1640 feet),
select a cable cross section so that
the voltage drop in the cable does not
exceed 5V.
To calculate the excitation cable
cross section area, use the following
formula:
A (cross section area: mm
2
) =
35.6 x L (cable distance: m) x 0.4 (A)
1000 x 5 (V)
Current output cable (4-20 mA)
The allowable current output load of
the converter is 0 to 600. The sum of
the cable resistance plus load
resistance must be within this range.
With a 2 mm
2
(0.003 in
2
) cable, the
cable resistance for both-ways
between 1 km (3.281 ft.) distance is
approximately 20. When the
receiver load is 400, the current
output cable can be extended up to 10
km (6.2 miles).
Pulse output cable
Can be extended up to 1 km
(3,281 ft.).
Grounding
The grounding circuit should be less
than 100.
At the converter side, ground the
meter at the E terminal of the terminal
block or the ground terminal of the
case. The E terminal and the ground
terminal are mutually connected in the
unit.

Table of Contents

Related product manuals