|74
ITEM
NUMBER
ITEM DESCRIPTION
POSSIBLE
VALUE
AUDIT TRAIL LOG VALUE
1 - 01
3 - 03
C - 12
B - 11
so, AT log will be stored as 01031211.
3131
CloudLink Last Call Physical ID
(Applicable for CLR100 only)
String
Decimal coded hex number
and stores the last 8 digits
3133 CloudLink Last Call TAC String Convert to decimal
3139 CloudLink RUID2 String Last 8 characters
Example: If CloudLink RUID is 8002473075 then, AT log value will be stored as 02473075.
3167 FOTA FTP Server IP IPv4 format Last two blocks as float
Logging periodicity:
Using MasterLink configuring software, an instrument can be configured to contain as many as 5
independent logs, each with its own collection of item values and collection (sample) frequency. Each log
can be configured to collect values for up to 20 items.
Logging Configuration when configured for less than an hour, the CL items will be refreshed on per hour
basis only. Whereas, if the log frequency is configured to an interval more than an hour (daily or monthly)
then, the log items will be observed with the same frequency (daily or monthly).
For example:
If log frequency is configured as five minutes then, CloudLink item values in the Logging configuration
will be refreshed ONLY at the end of the hourly time period.
If frequency is set to daily (24 hours) then, the items in the logging configuration will be refreshed on daily
basis.
CloudLink AT Log Error Conditions
If EVC/ERX is unable to read CloudLink items based on Audit Trail Log configuration then, error codes get
logged as per the below table:
CONDITION ERROR DESCRIPTION
Unsupported CloudLink Item Unsupported
MODEM configured is CNI2/Messenger/NoMODEM MODEM Mismatch
RD fails - Contention in Dial Out Contention
CloudLink fails to response in spite of many retries No Response
Port busy - all retries have failed Busy
12 350S Audit Trail Log support for CloudLink MODEM